Technical data
Housing
Protection rating (EN60529)
  • IP66
Case material
  • Type RA80
  • Explosion-proof and flame-proof
  • Epoxy painted, Aluminium
  • Captive stainless steel screws
Mounting
  • Wall mounting, 3 back lugs
Scale
  • Internal, accuracy on reading ± 5 % FS
Process
Process connection
  • G1/2"
  • 1/2" NPT
  • 1/4" NPT female
Temperature
Ambient temperature
  • -20°C ... +55°C (T6)
Storage temperature
  • -40°C ... +70°C
Media temperature
  • -15°C ... +100°C
Wetted parts
Flange
  • Stainless steel 1.4404 / AISI 316L
Diaphragm
  • FKM (Viton®)
Sensing / Input
Min. measuring range
  • -2.5 ... 2.5 mbar
Max. measuring range
  • 10 ... 400 mbar
Performance
Repeatability
  • ± 1 % FS
Adjustment
  • 2 external adjustment screws on top of the case for set point and deadband
  • When set point adjustment is required it is necessary to know the static pressure, as it has an influence on the set point.
Electrical data
Ground connection
  • Via internal terminal block
Electrical connection
  • Via internal terminal block with metallic cable gland for Ø 7 to 12 mm
Approval / Conformities
ATEX/IECEx Certificate
  • LCIE 03 ATEX 6231X (Type RA80)
  • IECEx LCIE 15.0061X
ATEX/IECEx
  • Ex II 2 GD
  • Further information can be found in the ATEX approval
CE conformity
  • ATEX directive 2014/34/UE

Downloads
Data sheet
Operating Manual
Certificates / approvals
Declaration of Conformity

Drawings
Drawings
The selected altAttribute does not exist!

Pressure range codes: 110 - 111 - 121 - 131

(png | 76 KB)
The selected altAttribute does not exist!

Pressure range codes: 156 - 157

(png | 71 KB)