Technical data
Housing
Protection rating (EN60529)
  • IP66
Cover
  • Blue painted, zamak
  • Captive stainless steel screws
Case material
  • Black painted, zamak
Mounting
  • Wall mounting bracket
Scale
  • Internal, accuracy on reading ± 5 % FS
Process
Process connection
  • G1/2"
  • 1/4" NPT female
  • 1/2" NPT
Process connection material
  • Stainless steel 1.4404 / AISI 316L
Temperature
Ambient temperature
  • -25°C ... +55°C (T6)
Storage temperature
  • -40°C ... +70°C
Media temperature
  • -15°C ... +100°C
Wetted parts
Flange
  • Stainless steel 1.4404 / AISI 316L
Diaphragm
  • FKM (Viton®)
Sensing / Input
Min. measuring range
  • 2 ... 10 mbar
Max. measuring range
  • 10 ... 400 mbar
Performance
Repeatability
  • ± 1 % FS
Adjustment
  • 2 external adjustment screws on top of the case for set point and deadband
  • When set point adjustment is required it is necessary to know the static pressure, as it has an influence on the set point.
Electrical data
Ground connection
  • Via internal terminal block
Electrical connection
  • Via internal terminal block with plastic cable gland for Ø 7 to 10.5 mm
Approval / Conformities
ATEX/IECEx Certificate
  • LCIE 03 ATEX 6123X
  • IECEx LCIE 15.0060X
ATEX/IECEx
  • Ex I M1
  • Ex II 1 G
  • Further information can be found in the ATEX approval
CE conformity
  • ATEX directive 2014/34/UE

Downloads
Data sheet
Operating Manual
Certificates / approvals
Declaration of Conformity

Drawings
Drawings
The selected altAttribute does not exist!

Pressure range codes: 111 - 121 - 131

(png | 70 KB)
The selected altAttribute does not exist!

Pressure range codes: 156 - 157

(png | 61 KB)

To the top