Technical data
Housing
Protection rating (EN60529)
  • IP66
Case material
  • Epoxy painted, Aluminium
  • Captive stainless steel screws
  • Type RA80
  • Explosion-proof and flame-proof
Mounting
  • Wall mounting, 3 back lugs
Scale
  • Internal, accuracy on reading ± 5 % FS
Performance
Min. pressure range
  • -50 ... 0 mbar
Max. pressure range
  • 0 ... 2500 mbar
Repeatability
  • ± 1 % FS
Temperature
Ambient temperature
  • -20°C ... +70°C (T5)
  • -20°C ... +60°C (T6)
Storage temperature
  • -40°C ... +40°C ,Code 40
Media temperature
  • -15°C ... +150°C
Wetted parts
Process connection material
  • Stainless steel 1.4404 / AISI 316L
Diaphragm
  • FKM (Viton)
Electrical data
Electrical connection
  • Via internal terminal block with metallic cable gland for Ø 7 to 12 mm
Ground connection
  • Via internal terminal block
Adjustment
  • 2 external adjustment screws on top of the case for set point and deadband
Approval / Conformities
ATEX/IECEx Certificate
  • LCIE 03 ATEX 6231X (Type RA80)
  • IECEx LCIE 15.0061X
ATEX/IECEx
  • ATEX directive 2014/34/UE
  • Ex II 2 GD
  • Ex d IIC T6 or T5 Gb
  • Ex tb IIIC T80°C or T95°C Db
  • Further information can be found in the ATEX approval

Downloads
Data sheet
Operating Manual
Certificates / approvals
Declaration of Conformity

Drawings
Drawings

Pressure range codes: 101 - 102 - 103 - 104

(png | 82 KB)

Pressure range codes: 151 - 152 - 153 - 154

(png | 73 KB)

Pressure range codes: 171 - 172 - 173

(png | 77 KB)

To the top